How to read your solar generation and your savings
Which number to trust, what yield, performance ratio and CUF tell you, and how to find the real saving in your bill.
A solar plant reports a great many numbers, and the electricity bill reports different ones. Owners often cannot tell from either whether the plant is doing what was promised or how much it saved last month. This guide explains where each number comes from, what the common measures mean, and how to work out savings from the bill.
It gives no tariffs, yields or target values. Those differ by plant, state and consumer category. Take them from your own yield estimate, your contract and the tariff order that applies to you.
Where the numbers come from
| Source | What it measures | Use it for |
|---|---|---|
| Inverter display or monitoring portal | Energy leaving each inverter, with power through the day. | Day-to-day watching, comparing inverters and spotting faults. |
| Solar generation meter | Total energy the plant delivered, on a sealed meter. | The generation figure of record, for contracts and for the distribution company. |
| Net meter | Units drawn from the grid and units sent to it, recorded separately. | Billing. It does not show how much the plant generated. |
| Electricity bill | Import, export, credits carried forward and the charges applied. | Working out what was saved in money. |
| Irradiation sensor or weather station | Sunlight that reached the modules. | Judging generation against the weather that occurred. |
When two sources disagree, the sealed meters prevail. A gap between the inverters and the generation meter that grows over time is itself worth investigating.
Power and energy
Kilowatt (kW) is the rate at which the plant is producing at an instant. Kilowatt-hour (kWh), the unit on your bill, is the energy produced over time. The plant's capacity in kilowatt-peak (kWp) is the output of its modules under standard test conditions, which a working plant rarely meets. A plant producing less than its kWp rating at midday is normal and is not a fault.
The measures that describe a plant
Specific yield
Energy generated divided by installed capacity, stated as kWh per kWp over a day, month or year. It lets you compare plants of different sizes and compare this year with last year. It moves with the weather, so compare the same months.
Performance ratio
Energy generated compared with what the sunlight that fell on the modules could have produced. Because it accounts for the weather, it is the fairest single measure of the plant's health. It needs a working irradiation sensor that is clean and correctly placed, and a ratio calculated from a faulty sensor misleads.
Capacity utilisation factor (CUF)
Energy generated compared with the plant running at full capacity for every hour of the period. Regulations and power purchase agreements are often written in CUF. Check whether your contract calculates it on the capacity of the modules or of the inverters, because the two give different results.
Availability
The share of daylight hours for which the plant, and the grid it connects to, were able to run. A plant can perform well while running and still lose generation to breakdowns or grid outages. Ask for plant availability and grid availability to be reported separately.
Judging generation fairly
- Compare with the estimate for the same month. Generation follows the season. A month that looks poor against the month before may be on target.
- Correct for the weather. A cloudy month generates less through no fault of the plant. Performance ratio makes that correction.
- Allow for ageing. Modules lose a little output each year, at a rate stated in their warranty. The estimate for a later year should already include it.
- Take out what was not the plant's doing. Grid outages and instructed shutdowns reduce generation and should be logged.
- Compare inverters with one another. Similar inverters with similar strings should track each other. One that falls behind points to a fault.
If generation stays below the estimate after these corrections, see our guide to diagnosing an underperforming plant.
From generation to savings
Generation is what the plant produced. Savings are what you did not pay. The two are linked by how the power was used.
Units used directly
Solar power consumed inside the premises as it is generated replaces units you would have bought. Each is worth the energy charge you avoided, with the levies charged on it. This is normally the most valuable use of the plant's output.
Units exported
Power the premises could not use flows to the grid and is recorded as export. How it is credited depends on the arrangement and the state: set off against units drawn, carried forward to later months, or paid at a rate fixed by the regulator, with a settlement at the end of a period. Read the rule that applies to you, because an exported unit is often worth less than a unit used directly.
What solar does not reduce
Fixed charges, demand charges and some surcharges are not billed on units and largely remain. Under open access or a power purchase agreement there are also charges for using the network. Leave these out of the saving unless the bill shows they fell.
A method for any month
- Take generation from the solar generation meter and export from the net meter, for the same dates as the bill.
- Subtract export from generation to find the units used directly.
- Value the units used directly at the energy charge and levies on your bill for the time slots in which they were generated.
- Value the exported units as your net metering or contract terms credit them.
- If you buy the power under a power purchase agreement, subtract what you paid the plant owner.
Common misreadings
- Comparing the bill with last month's bill. Consumption and season both changed. Compare with the same month a year earlier, and with what the bill would have been without the plant.
- Reading the net meter as generation. It sees only what crossed the boundary of the premises.
- Mixing dates. The portal reports calendar months and the bill runs between meter readings.
- Counting exported units at the full tariff. Check how they are credited.
- Judging the plant by one day. Use a month, and correct for the weather.
What to ask for every month
- Generation against the estimate for that month.
- Specific yield and performance ratio, with the irradiation recorded.
- Plant availability and grid availability.
- Generation by inverter.
- Faults raised, and when each was closed.
- Cleaning carried out.
- Import, export and credits from the bill, with the saving worked out.
Where Sunmaster stands
Sunmaster, a brand of Saev Private Limited (Saev P Ltd), operates and maintains solar plants under its Solar Care O&M service, for plants it built and for plants built by other contractors.
Related pages
- Solar plant underperforming? How to diagnose it
- CAPEX or PPA: how to choose the way you pay
- Virtual Net Metering in Delhi: a practical guide to the rules
- Case study: design figures and measured performance at Issapur
This guide is general information. Tariffs, credits and settlement rules are set by each state's regulator and change. Check the current order for your category before relying on a calculation.
Common questions
Why does the inverter show more units than my bill credits?
They measure different things. The inverter counts everything the plant generated. The bill deals only with what crossed the meter: units you drew from the grid and units you sent to it. Solar power used inside the premises at the moment it was generated never reaches the bill as a line, and shows up only as fewer units drawn. Small differences also come from losses between the inverter and the meter and from different reading dates.
What is the difference between performance ratio and CUF?
Performance ratio compares what the plant generated with what the sunlight falling on it could have produced, so it describes the health of the plant and is largely independent of the weather. CUF compares generation with the plant running at full capacity around the clock, so it moves with the site and the season as well as with the plant. Use performance ratio to judge the plant and CUF to compare with contracts and regulations that are written in it.
Why did my savings fall when generation did not?
Savings depend on more than generation. If the factory ran fewer hours, more solar power was exported and less was used directly, and exported units are often worth less than units you would otherwise have bought. A change in tariff, in the time-of-day slots or in how exported units are settled has the same effect. Check consumption and the tariff order before suspecting the plant.
Does solar reduce the fixed or demand charges on my bill?
Usually not by much. Fixed and demand charges are billed on sanctioned or recorded demand, not on units, and the highest demand of the month may fall when the plant is producing little. Count savings on energy charges and the levies tied to them, and treat any fall in demand charges as something to verify from the bill, not to assume.